Decoding Voltage Sag/Dip Graphsđ
- Truewatts
- Jul 22, 2025
- 3 min read
Updated: Jan 5
Understand Voltage Sag Graphs with EaseâGain Insights to Analyze, Plan, and Make Better Decisions
At Truewatts, weâve had the opportunity to support many clients in analyzing data from Power Quality Meters (PQ Meters), especially when dealing with voltage sags or dips. Quite often, the questions that follow are:
đ âWhat exactly does this graph mean?â
đ âHow can we make practical use of this data?â
This article walks you through how to interpret Voltage Sag/Dip graphs effectively. We will also explore how these insights can drive technical decisions and planning with real impact.
đ§Š Whatâs the Difference Between a Voltage Sag and a Voltage Dip?
While the terms Voltage Sag and Voltage Dip are used differently depending on the region and standards, they refer to the same event: a temporary drop in voltage in an electrical system. Hereâs how they differ in usage:
â Voltage Sag: Commonly used in North America (IEEE, EPRI, etc.)
â Voltage Dip: Used in Europe and in international standards (e.g., IEC)
According to IEEE 1159, a voltage sag is defined as:
"A decrease to between 0.1 and 0.9 per unit in RMS voltage or current at the power frequency, for durations of 0.5 cycle to 1 minute."
đ Sample Graph from a PQ Meter
The graph below is captured from the MDB (Main Distribution Board) using a Power Quality Meter.


It clearly shows a voltage drop (Voltage Sag/Dip).
đ Data at a Glance:
Voltage dropped to 70.62% of nominal
Duration: 0.689 seconds
Timestamp of the event recorded
đ§ Why Do Magnitude and Duration Matter?
To evaluate the impact of a Voltage Sag, two key parameters must be considered:
đš Magnitude
This refers to the depth of voltage reduction compared to the nominal voltage. It is expressed as a percentage of the nominal voltage. For example: 70%, 50% of nominal.
If the voltage dips below a deviceâs tolerance level, it may trip or reset.
PLCs typically withstand only 80â90%; inverters around 70â80%.
đš Duration
This indicates how long the sag lasts. For example: 0.1 sec vs. 0.7 sec.
Sags lasting 20â40 ms might be tolerable for some equipment.
Sags lasting over 100â200 ms significantly increase trip risks.
đĄ In this case, a sag to 70% lasting 0.689 seconds is both deep and longâwell beyond the tolerance of most industrial equipment.
đ This data can be compared to standards like:
SEMI F47
IEC 61000-4-11
This comparison helps determine if protective equipment or design changes are needed.
đŻ How Can You Use This Data?
1ď¸âŁ Identify Root Causes of Equipment Shutdown
If a PLC reset, inverter tripped, or production line stopped at the same timestamp, you can confirm that Voltage Sag was the root cause. This approach saves time chasing mechanical or software issues.
2ď¸âŁ Support Investment Decisions for Protection Equipment
For example:
Voltage Compensation System
UPS for Control Circuits
In this case, a 0.7-second sag exceeds the tolerance of most PLCs (20â100 ms). This justifies installing sag-mitigation solutions in key areas.
3ď¸âŁ Use as Technical Evidence
If damages or downtime occur, include this graph in reports to utilities or equipment manufacturers. Reference sag immunity specs (e.g., SEMI F47, IEC 61000-4-11).
4ď¸âŁ Compare with Sag Tolerance Standards
Use:
Voltage: 70.62%
Duration: 0.689 sec
Compare against:
CBEMA / ITIC Curve
SEMI F47
IEC 61000-4-11 test levels
â If the equipment shouldâve tolerated the sag but still tripped, review circuit design (especially control circuits).
5ď¸âŁ Plan Power System Improvements
Install permanent PQ meters or adjust measurement locations.
Separate critical vs. non-critical loads.
Assess the feasibility of Fast Transfer Switches or ATS systems.
đŹ Need Help Decoding Your PQ Data?
If you are looking to get the most value out of PQ event dataâor are considering equipment to improve voltage sagâWe are here to help. Info@truewatts.co.th




Comments